GAIL's Tatipaka-Kondapalli pipeline, which was built in 2001 to move dry natural gas to Lanco Power Plant, transported gas as also water and condensate coming from ONGC's wells. Water and condensate corroded the pipeline, leading to gas and condensate leaking to surface where a lighting of a stove led to a blast and subsequent fire on June 27.
An inquiry committee, headed by the ministry's Joint Secretary (Refineries) Rajesh Kumar Singh, in its report blamed "inadequate systems/approach" for the accident.
Putting separators to strip gas of liquids before transportation may not be economically viable at all places due to small quantities of fuel being produced from these fields.
An audit by pipelines regulator PNGRB in August 2011 too did not make any observation in connection to composition of gas and associated issues.
The report said there was "no evidence of any efforts" by Nagpur-based Petroleum and Explosives Safety Organisation (PESO) to enforce putting up of Gas Dehydration Unit to drain out water and liquids.
The report said it was difficult to establish individual culpability.
Besides installation of dehydration facility for removal of water and condensate prior to feeding natural gas in the pipeline, it recommended through inspection of the pipelines and putting up of leak detection system.
Also, patrolling using modern gadgets should be carried out in the pipeline route.
It also recommended that "GAIL should complete an internal enquiry of managerial failures at different levels and fix responsibility for the lapses pointed out herein."
"Comprehensive procedure shall be developed for repair of pipeline in case of leak," it said, adding GAIL must develop proper supervisory and control systems for maintaining the health of pipelines.
"GAIL has apparently flouted the declaration to the statutory authority as well as the declared design basis by not providing GDU at Tatipaka and Mori. Absence of GDU contributed to increasing the internal corrosion rate in the pipeline," the report said.
Wet gas contains free water, carbon dioxide and sulphur which induced internal corrosion in the pipeline.
The panel said the explosion, followed by a major fire, was due to leakage of condensate and gas which was probably continuing from the night before the incident. The condensate formed vapour cloud with gas pockets, and triggered a major fire when a tea vendor lighted the stove.
You’ve reached your limit of {{free_limit}} free articles this month.
Subscribe now for unlimited access.
Already subscribed? Log in
Subscribe to read the full story →
Smart Quarterly
₹900
3 Months
₹300/Month
Smart Essential
₹2,700
1 Year
₹225/Month
Super Saver
₹3,900
2 Years
₹162/Month
Renews automatically, cancel anytime
Here’s what’s included in our digital subscription plans
Exclusive premium stories online
Over 30 premium stories daily, handpicked by our editors


Complimentary Access to The New York Times
News, Games, Cooking, Audio, Wirecutter & The Athletic
Business Standard Epaper
Digital replica of our daily newspaper — with options to read, save, and share


Curated Newsletters
Insights on markets, finance, politics, tech, and more delivered to your inbox
Market Analysis & Investment Insights
In-depth market analysis & insights with access to The Smart Investor


Archives
Repository of articles and publications dating back to 1997
Ad-free Reading
Uninterrupted reading experience with no advertisements


Seamless Access Across All Devices
Access Business Standard across devices — mobile, tablet, or PC, via web or app